Corrosion protection

Preventing coastal coil corrosion in Qatar with Heresite® coating

Along Qatar's coastline, salt-laden humid air attacks the copper and aluminium inside HVAC coils. Corrosion is often invisible until capacity drops, fins crumble or refrigerant leaks. A certified protective coating is one of the most effective ways to stop it.

Published:

Preventing coastal coil corrosion in Qatar with Heresite® coating

Why coils corrode faster near the Gulf

Coils combine two metals, copper tubes and aluminium fins, in a wet, salty environment. Salt deposits hold moisture on the fin surface, and the contact between dissimilar metals speeds up galvanic corrosion at the fin-to-tube joint.

High temperatures, dust and continuous duty make it worse. Rooftop units on waterfront towers, hotels, hospitals and industrial sites are the most exposed.

  • Fins turn white, flake or crumble when touched
  • Rising head pressure and falling cooling capacity
  • Refrigerant leaks at tube bends and joints
  • Higher energy use for the same cooling load

How Heresite® coating protects coils

Heresite® coatings form a continuous protective barrier over the whole coil, including the fin edges and the joints between fins and tubes, so salt and moisture never reach the bare metal.

Arrow Heat Exchanger Factory is a certified Heresite® applicator for P-413, a baked phenolic epoxy coating, and HereShield® WB-506, a water-based protective coating. The coating is applied and cured in our Doha factory under controlled conditions.

New coils or existing equipment

Coating works best on new coils before they are installed, and we can also coat replacement coils built to match your existing unit. For equipment already on site, we assess the coil condition first: badly corroded coils should be replaced rather than coated.

  • New condenser and cooling coils, coated before delivery
  • Replacement coils with the same geometry, casing and connections
  • Assessment of existing coils before deciding to coat or replace

Getting started

Send us the unit make and model, or the coil dimensions, and a photo of the current coil. Our engineers will recommend the right coating and whether a new coil is needed.

Need a quote for your project?

Send your equipment details through our Engineering RFQ and our engineers will reply with options.

Call Factory WhatsApp Request Quote